We are pleased to offer procurement for General Electric Company part number THED136070XL here on NSN Portal, a Circuit Breaker product that is listed with the NSN 5925-01-019-8910 for ease of identification. You have reached our Request for Quote (RFQ) form for this listing, where you are encouraged to submit details on your requirements to receive tailored purchasing options from our staff. As you will see, we ask that you offer key information on your pricing target, desired quantity, and more, as this will ensure that the representative who responds to your request is able to provide the most fitting solutions for your needs.
Note : We Will Not Share Your Information To Any Third Parties.
Whether you procure part number THED136070XL or other NSN products from our website, you can rest assured that we uphold full traceability for all items. For example, this particular listing traces back to General Electric Company through the CAGE Code 60969, as well as falls under FSC 5925 Circuit Breakers based on having the NSN 5925-01-019-8910. Furthermore, every purchase will be delivered with any applicable qualifying certifications or manufacturer trace documentation as per our NO CHINA SOURCING pledge. If you are ready to experience why professionals rely on us for their needs, request a quote for part number THED136070XL today and take advantage of our industry-leading services.
MRC | Criteria | Characteristic |
---|---|---|
AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
ADAQ | BODY LENGTH | 6.3125 INCHES NOMINAL |
ADAT | BODY WIDTH | 4.125 INCHES NOMINAL |
ADAU | BODY HEIGHT | 3.1875 INCHES NOMINAL |
ADTV | CASE MATERIAL | PLASTIC |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 4.87501 INCHES NOMINAL |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.375 INCHES NOMINAL |
AJEC | BOSS HEIGHT | 0.90625 INCHES NOMINAL |
AKPX | POLE QUANTITY | 3 |
CBBL | FEATURES PROVIDED | ADJUSTABLE TRIP RELEASE AND INTERCHANGEABLE TRIP RELEASE |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 70.0 AMPERES AC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 600.0 AC ALL LOCATIONS AND 250.0 DC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 18000.0 AC ALL LOCATIONS AND 20000.0 DC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPRW | ACTUATOR FUNCTION | RESET |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 88.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 350.000 MAXIMUM AT 200 PCT ALL LOCATIONS AND 27.500 MINIMUM AT 300 PCT ALL LOCATIONS AND 140.000 MAXIMUM AT 300 PCT ALL LOCATIONS AND 14.500 MINIMUM AT 400 PCT ALL LOCATIONS AND 77.500 MAXIMUM AT |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 10.0 DEG CELSIUS MINIMUM ALL LOCATIONS AND 50.0 DEG CELSIUS MAXIMUM ALL LOCATIONS |
TTQY | TERMINAL TYPE AND QUANTITY | 3 SCREW BASE |